2003-09-18 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
  
 3)NOTE: PLEASE SEE 600.5 FOR REQ'D
 SIGN CIRCUIT. PLEASE SHOW IF NEW OR
 EXISTING.
  
 4)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 INFORMATION REQ'D ON TITLE BLOCK.PLEASE
 PROVIDE FIRM LICENSE # IF APPL.
  
 5)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. (LIGHTING) PER 215.3/230.42 ETC
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  