Plan Review Notes For Permit 03090340 |
Permit Number |
03090340 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-18 00:00:00 | ************* UNSAT **************** | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | THAT WILL HAVE AN AFFECT ON ELECTRICAL | | PLANS. | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | PLANS AND CORRELATE WITH A PANEL | | SCHEDULE TO BE SUBMITTED. | | | | 3)NOTE: PLEASE SEE 600.5 FOR REQ'D | | SIGN CIRCUIT. PLEASE SHOW IF NEW OR | | EXISTING. | | | | 4)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | INFORMATION REQ'D ON TITLE BLOCK.PLEASE | | PROVIDE FIRM LICENSE # IF APPL. | | | | 5)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | -ING OF EM/EXT LTS. | | | | 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125%. (LIGHTING) PER 215.3/230.42 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|