Plan Review Notes For Permit 03090320 |
Permit Number |
03090320 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-15 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE SEE OCP PROTECTION SHOWN | | FOR RANGE. SHOWS 10KW W/ 40OCP? PLEASE | | SEE MIN LOAD IS 42A'S WHICH IS OVER THE | | 40A OCP. | | | | 2)NOTE: PLEASE SEE 210.52C3,4 FOR GFI | | RECEPT MISSING ON PENINSULAR. SEPARATE | | SPACES. | | | | 3)NOTE: PLEASE SEE MISSING RECEPT PER | | 210.52 FOR 2' OF WALL. | | | | 4)NOTE: PLEASE CLARIFY OCP SHOWN FOR | | 10KW HEAT FOR AHU. SHOWN AS 2P-50A, | | PLEASE SEE 424.3B FOR 125% MIN OCP. | | | | 5)NOTE: NEW MASTER BEDROOM, LIST ARC | | FAULT PROTECTION AS REQD' PER 210.12 | | OF NEC. | | | | 6)NOTE: PLEASE SEE NFPA-72, SD @ KITCHEN | | TO BE A MIN OF 3' FROM KITCHEN AREA. | | CAN BE MOVED OVER OR NOTED TO BE 3'. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|