2003-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03090250
 ADD: 222PICADILLY ST
 CONT: CREATIVE CONST CORP
 TEL: (561)236-8554
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2)11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
  
 3)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  