Plan Review Notes For Permit 03090250 |
Permit Number |
03090250 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 03090250 | | ADD: 222PICADILLY ST | | CONT: CREATIVE CONST CORP | | TEL: (561)236-8554 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | ACTION: DENIED | | | | 1)11-4.13.6 MANEUVERING CLEARENCES | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | AT DOORS THAT ARE NOT AUTOMATIC OR | | POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | IN THE REQUIRED CLEARENCES SHALL BE | | CLEAR & LEVEL. | | | | 2)11-4.13.5 DOORWAYS, MINIMUM | | CLEAR WIDTH: DOORWAY SHALL HAVE A MINI- | | MUM CLEAR OPENING OF 32" WITH THE DOOR | | OPEN 90 DEGREES, MEASURED BETWEEN THE | | FACE OF THE DOOR AND THE OPPOSITE STOP. | | | | 3)1204.2 SURROUNDING MATERIALS; | | THE WALLS & FLOORS OF ALL PUBLIC REST- | | ROOMS SHALL BE LINED WITH NONABSORBANT | | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE | | FLOOR. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|