2003-09-11 00:00:00 | ********* UNSAT ***************** |
| |
| 1)NOTE: PLEASE SHOW LOCATION OF MAIN |
| PANEL ON PLANS. |
| |
| 2)NOTE: PLEASE SHOW SIZE OF OCP FOR FEED |
| TO NEW PANEL. SHOWS 6/3 ROMEX WHICH IS |
| NOW PERMITTED, HOWEVER, ROMEX MUST BE |
| PROTECTED FROM ALL PHYSICAL DAMAGE AND |
| MUST MEET NEC. |
| |
| 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI'S. |
| 210.8A6 |
| |
| 4)NOTE: PLEASE LIST THE REQ'D DEDICATED |
| BATH CIRCUIT(S) PER 210.52D/ 210.11C3 |
| #1220A |
| |
| 5)NOTE: PLEASE SHOW REQ'D SD'S INSIDE |
| AND OUTSIDE SLEEPING ROOMS. NFPA-72 |
| 8-1.4.2 |
| |
| 6)NOTE: PLEASE CORRELATE PLANS SUBMITTED |
| , REVERSE SIDE OF DRAWING SHOWS A |
| COMPLETELY DIFFERENT LAYOUT?? |
| |
| 7)NOTE: PLEASE SEE PLAN, APPEARS TO SHOW |
| PANEL IN BATHROOM? THIS IS NOT PERMITTED |
| PER 240.24 NEC |
| |
| 8)NOTE: PLEASE SEE 210.52E FOR FRONT AND |
| REAR RECEPT REQ'D. |
| |
| 9)NOTE: PLEASE CLARIFY IF THERE IS A |
| SECOND MEANS OF EGRESS. IF SO, PLEASE |
| SEE 210.70 FOR LT/SW REQ'D. |
| |
| 10)NOTE: PLEASE SEE LOAD CALCS, SHOWS |
| RANGES AS GAS, HOWEVER WATER HEATER AND |
| WASHER/ DRYER IS SHOWN AS N/A, |
| PLEASE CLARIFY IF GAS ALSO. |
| PLEASE SEE 220.16B FOR MIN CIRCUIT REQ'D |
| FOR WASHER. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |