Plan Review Notes
Plan Review Notes For Permit 03090002
Permit Number 03090002
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-06 00:00:00OK FOR HISTORIC (PLANS NOT STAMPED)
 PER SP
2003-10-02 00:00:00******CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)ENGINEER'S LICENSE NUMBER IS
 REQUIRED ON THE TITLE BLOCK, FAC
 61G15-23.002.
  
 3.)SHOW THE WINDOW SIZES, TYPE AND
 SILL HEIGHT FOR BEDROOMS.COMPLY WITH
 FBC1005.4.
  
 4.)IT IS NOT CLEAR AS TO HOW SIMPSON
 H10 IS TO BE INSTALLED (EXTERIOR WALL
 SECTION).CLARIFY.
  
 5.)PROVIDE DIMENSIONS FOR THE EXTERIOR
 WALL.FIRESTOP MAY BE REQUIRED FBC
 705.3.
  
 6.)CHANGES DRAWN ON THE PLAN MUST
 BE INITIALED AND DATED BY THE ENGINEER.
  
 7.)PROVIDE SPACING FOR THE 1/2"X6" EXP
 BOLTS (EXTERIOR WALL SECTION).
  
 8.)IMPACT PROTECTION REQUIRED FBC1606.
 1.4.PROVIDE A HURRICANE SHUTTER
 ATTACHMENT DETAIL.
  
 9.)THE ATTACHMENT SPECIFIED IN THE
 WOOD HEADER DETAIL, TP#X, IS NOT IN THE
 USP2003 CATALOG.CLARIFY.
  
 10.) NAILING FOR THE USP RS100 CONFLICTS
 WITH THE CATALOG.CLARIFY.
  
 11.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 12.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS AS IT APPEARS THAT THEY ARE
 TO BE REPAIRED OR REPLACED. FIREBLOCKING
 REQUIRED AT STAIRS FBC2305.1.4.
  
 13.)IMPROVEMENTS OVER 50% OF VALUE
 ARE TO COMPLY WITH FBC3401.7.2.6.
  
 14.)PROVIDE A HANDRAIL DETAIL.
  
 15.)PROVIDE A SURVEY FOR THIS JOB.
  
 16.)THE WINDOW PRODUCT APPROVAL IS NOT
 COMPLETE.
  
 17.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR:
 SINGLE HUNG WINDOW
 FRONT DOOR
 IMPACT PROTECTION
 PRODUCT APPROVALS MAY BE AVAILABLE AT
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE COMPLIANCE, PRODUCT CONTROL, SEARCH
 APPROVED PRODUCTS).