2003-10-06 00:00:00 | OK FOR HISTORIC (PLANS NOT STAMPED) |
| PER SP |
2003-10-02 00:00:00 | ******CORRECTIONS***** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)ADDITIONAL PERMITS REQUIRED. |
| |
| 2.)ENGINEER'S LICENSE NUMBER IS |
| REQUIRED ON THE TITLE BLOCK, FAC |
| 61G15-23.002. |
| |
| 3.)SHOW THE WINDOW SIZES, TYPE AND |
| SILL HEIGHT FOR BEDROOMS.COMPLY WITH |
| FBC1005.4. |
| |
| 4.)IT IS NOT CLEAR AS TO HOW SIMPSON |
| H10 IS TO BE INSTALLED (EXTERIOR WALL |
| SECTION).CLARIFY. |
| |
| 5.)PROVIDE DIMENSIONS FOR THE EXTERIOR |
| WALL.FIRESTOP MAY BE REQUIRED FBC |
| 705.3. |
| |
| 6.)CHANGES DRAWN ON THE PLAN MUST |
| BE INITIALED AND DATED BY THE ENGINEER. |
| |
| 7.)PROVIDE SPACING FOR THE 1/2"X6" EXP |
| BOLTS (EXTERIOR WALL SECTION). |
| |
| 8.)IMPACT PROTECTION REQUIRED FBC1606. |
| 1.4.PROVIDE A HURRICANE SHUTTER |
| ATTACHMENT DETAIL. |
| |
| 9.)THE ATTACHMENT SPECIFIED IN THE |
| WOOD HEADER DETAIL, TP#X, IS NOT IN THE |
| USP2003 CATALOG.CLARIFY. |
| |
| 10.) NAILING FOR THE USP RS100 CONFLICTS |
| WITH THE CATALOG.CLARIFY. |
| |
| 11.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 12.)PROVIDE A STRUCTURAL DETAIL FOR |
| THE STAIRS AS IT APPEARS THAT THEY ARE |
| TO BE REPAIRED OR REPLACED. FIREBLOCKING |
| REQUIRED AT STAIRS FBC2305.1.4. |
| |
| 13.)IMPROVEMENTS OVER 50% OF VALUE |
| ARE TO COMPLY WITH FBC3401.7.2.6. |
| |
| 14.)PROVIDE A HANDRAIL DETAIL. |
| |
| 15.)PROVIDE A SURVEY FOR THIS JOB. |
| |
| 16.)THE WINDOW PRODUCT APPROVAL IS NOT |
| COMPLETE. |
| |
| 17.)PROVIDE TWO COPIES OF PRODUCT |
| APPROVALS FOR: |
| SINGLE HUNG WINDOW |
| FRONT DOOR |
| IMPACT PROTECTION |
| PRODUCT APPROVALS MAY BE AVAILABLE AT |
| WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING |
| CODE COMPLIANCE, PRODUCT CONTROL, SEARCH |
| APPROVED PRODUCTS). |