2003-09-09 00:00:00************ NOTES *****************
  
 1)NOTE: PLEASE VERIFY AIC RATING FOR
 NEW DISC'C FOR A,B,C PANELS.
 NOTE "N" MENTIONS 65K RATING? IS THIS
 FOR NEW MAINS?
 110.9/215.5
  
 2)NOTE: PLEASE CLARIFY LOCATION OF
 BARRRIER SHOWN TO BE INSTALLED IN GUTTER
 IT APPEARS PANEL "C" WILL BE FED FROM
 MAIN 1OF 3 AND PANELS A & B WILL BE FED
 FROMMAIN 2 OF 3?
  
 PLEASE SEE FIRE REVIEW COMMENTS FOR ANY
 POSSIBLE CHANGES TO ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  