Plan Review Notes For Permit 03081832 |
Permit Number |
03081832 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-09 00:00:00 | ************ NOTES ***************** | | | | 1)NOTE: PLEASE VERIFY AIC RATING FOR | | NEW DISC'C FOR A,B,C PANELS. | | NOTE "N" MENTIONS 65K RATING? IS THIS | | FOR NEW MAINS? | | 110.9/215.5 | | | | 2)NOTE: PLEASE CLARIFY LOCATION OF | | BARRRIER SHOWN TO BE INSTALLED IN GUTTER | | IT APPEARS PANEL "C" WILL BE FED FROM | | MAIN 1OF 3 AND PANELS A & B WILL BE FED | | FROMMAIN 2 OF 3? | | | | PLEASE SEE FIRE REVIEW COMMENTS FOR ANY | | POSSIBLE CHANGES TO ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|