2003-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER-11
  
 1) FROM PREVIOUS REVIEW: SHT A.5.3, DE-
 TAIL #6, BREAKROOM SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 PROVIDE DETAILS, SHOW CLEAR FLOOR SPACE,
 HEIGHT & CLEARANCES, FAUCETS, PIPES AND
 SURFACES, ECT.
 2) FROM PREVIOUS REVIEW: FOR GAS REVIEW,
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 3) SHT P3 PLUMBING SPECS #7, AIR CHAMB-
 ERS NOT APPROVED. DELETE REFERENCE.
 4) SHT P5 WATER RISER DIAGRAM, AIR CHAM-
 BERS NOT APPROVED. SEC 604.9 IF WATER
 HAMMER ARRESTORS THEY SHALL BE LOCATED
 NEAR THE FIXTURE, NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
  