Plan Review Notes
Plan Review Notes For Permit 03081679
Permit Number 03081679
Review Stop B
Sequence Number 2
Notes
Date Text
2003-11-04 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL ON 10/23/03 FOR ACCESSIBILITY
 REQUIREMENTS AS PER PROVISOS FROM
 9/04/03 PLAN REVIEW.
  
 --PROVISO--
 THE SUBMITTED MANUFACTURER'S CUT SHEET
 FOR THE 'AQUABATH IS4136BF' TRANSFER
 SHOWER SHOWS A 3/4" EXTERIOR HEIGHT
 DIMENSION AT THE STALL CURB.WHEN THE
 STALL IS INSTALLED, THE CURB SHALL BE NO
 HIGHER THAN 1/2" (SEE FBC 11-4.12.7).
 IT IS NOTED THAT SHEET 2 OF THE
 MANUFACTURERS DETAILS STATES "THE
 IS4136BF 3/4, AS SHOWN, IS NOT ADA
 COMPLIANT".PLEASE NOTE THAT THE CUT
 SHEETS HAVE BEEN REVIEWED FOR COMPLIANCE
 WITH THE FLORIDA BUILDING CODE WHICH
 INCLUDES FLORIDA ACCESSIBILTY CODE.ALL
 WORK IS SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.