Date |
Text |
2003-09-04 00:00:00 | BUILDING PLAN REVIEW |
| ******PROVISO******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| --PROVISO-- |
| FBC 11-6.1(1)FOR A PSYCHIATRIC |
| FACILITY MIN. 10% OF THE PATIENT ROOMS |
| ARE REQUIRED TO BE ACCESSIBLE.THE FOUR |
| NEW ROOMS ARE NOT ACCESSIBLE AS THERE IS |
| NOT 18" CLEARANCE BETWEEN THE STRIKE |
| EDGE OF THE ROOM ENTRY DOOR AND THE |
| ADJACENT WALL ON THE PULL-SIDE (REF. |
| FIG. 25(A)). CONFIRM THAT A TOTAL OF 10% |
| OF THE PATIENT ROOMS ARE ACCESSIBLE (SEE |
| ALSO, THE COMMENT BELOW). |
| |
| --PROVISO-- |
| FBC* 104.2.1SHEET A2.2, PATIENT |
| BATHROOM DETAILS 1 TO 4 STATE "TOILET TO |
| MEET FBC 11-4.16", "LAVATORY TO MEET |
| FBC 11-4.19" AND SPECIFY "AQUABATH |
| C4136BF TRANSFER SHOWER".IF THE NEW |
| PATIENT ROOMS ARE REQUIRED TO BE |
| ACCESSIBLE (SEE COMMENT ABOVE), THE |
| PLANS SHALL NOT SIMPLY CITE THE CODE |
| AND THE MANUFACTURER'S REFERENCE, THEY |
| SHALL INCLUDE DIMENSIONS/CLEARANCES/ |
| HEIGHTS FOR THE TOILET, LAVATORY AND |
| TRANSFER SHOWER.FOR THE SHOWER, |
| SUBMITTAL OF THE MANUFACTURERS DETAILS |
| WOULD BE SUFFICIENT. |