Plan Review Notes
Plan Review Notes For Permit 03081596
Permit Number 03081596
Review Stop M
Sequence Number 1
Notes
Date Text
2003-09-03 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3.
  
 2.INDICATE SIZE, MATERIAL, & LOCATION
 OF OUTSIDE AIR DUCT.
  
 3.INDICATE DUCT SMOKE DETECTOR (IF
 REQUIRED).
  
 4.STANDS FOR CONDENSING UNIT SHALL
 COMPLY WITH 2001 FBC 1511.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.