2003-09-16 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE PROVIDE LOAD CALCULATIONS FOR
 FOR ALL UNITS PER 215-5.
  
 3} PLEASE INDICATE THE SIZE AND TYPE OF
 ALL RACEWAYS AND CONDUCTORS BEING
 INSTALLED.
  
 4} PLEASE INDICATE THE GEC SYSTEM SIZE
 AND COMPLIANCE WITH ARTICLE 250.50.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  