2003-10-03 00:00:00 | 1) ALL NEW LODGING OR ROOMING HOUSES |
| SHALL BE PROTECTED WITH AN AUTOMATIC |
| FIRE SPRINKLER SYSTEM. |
| |
| 2) BUILDING ADDRESS NOT SHOWN ON |
| ELEVATION DRAWINGS. A MINIMUM OF 6" |
| NUMERALS REQUIRED. |
| |
| 3) RISE AND TREAD SIZES ARE WRONG FOR |
| THE STAIRS. TREADS SHALL BE A MINIMUM |
| OF 11" WIDE. RISERS SHALL BE A MINIMUM |
| OF 4" AND A MAXIMUM OF 7". |
| |
| 4) WINDOW AND AT LEAST ONE DOOR NOTED |
| WITHIN 10 FEET OF EXIT STAIR. |
| |
| 5) SMOKE DETECTORS ON FIRST FLOOR |
| MAY BE LOCATED TOO CLOSE TO BATHROOMS |
| WHERE STEAM WOULD CAUSE FALSE ALARMS. |
| |
| 6) PLEASE EXPLAIN EXITING RATIONALE |
| FROM SECOND FLOOR. IT APPEARS A SINGLE |
| EXIT IS PROVIDED. IS NO SECONDARY EXIT |
| OR MEANS OF ESCAPE PROVIDED. |
| |
| 7) NO HANDRAILS PROVIDED AT THE TWO |
| SETS OF STEPS FROM THE FRONT PORCH. |
| |
| 8) NO FIRE ALARM SYSTEM INDICATED ON |
| DRAWINGS. |
| |
| 9) NO INTERIOR FINISH INFORMATION |
| PROVIDED FOR WALLS AND CEILINGS. |
| |
| 10) PLEASE INDICATE ANY TENANT OR |
| FLOOR SEPARATIONS BETWEEN SUITES. |
| |
| 11) BATHROOM AND CLOSET DOORS SHALL |
| MEET CERTAIN REQUIREMENTS. CLOSET |
| DOORS SHALL BE OPERABLE FROM THE |
| INSIDE. BATHROOM DOORS SHALL BE |
| OPENABLE FROM THE OUTSIDE. |
| |
| 12) BUILDING MAY BE LOCATED IN THE |
| CITY FIRE LIMITS. CERTAIN RESTRICTIONS |
| MAY APPLY. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |