2003-10-07 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE THAT PANEL SHALL NOT
 BE LOCATED IN BATHROOM.240.24E
  
 3)NOTE: PLEASE CORRELATE OCP FOR A/C
 UNITS WITH WHAT IS SHOWN ON MECH DETAIL.
 ONE SHOWN AS 25A OCP OTHER SHOWN AS 30A
  
 4)NOTE: PLEASE SEE THAT SD'S ARE NOT TO
 BE LOCATED W/IN 3' OF BATHROOM DOORS.
 NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE SEE THAT CIRCUITS ARE
 SHOWN ON PANEL W/#14AWG AND 20A OCP.
 PLEASE SEE 310.16 AND NOTES TO TABLE.
  
 6)NOTE: PLEASE SEE THE MIN REQ'D FOR
 BATH GFI. 210.52D, 210.11.C3 , PLEASE
 SEE THAT ALL BATH GFI'S ARE BEING SHOWN
 ON ONE CIRCUIT?
  
 7)NOTE: NOTE TO PANEL/MAIN AIC RATING IS
 SHOWN AS A/C RATING. PLEASE CORRECT.
  
 8)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER 220.
  
 9)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 481. PLEASE SEE THAT TITLE BLOCK IS
 MISSING REQ'D LICENSE # INFORMATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  