Plan Review Notes For Permit 03081544 |
Permit Number |
03081544 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-07 00:00:00 | *************** UNSAT *************** | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH SUBMITTED | | PANEL SCHEDULE. | | | | 2)NOTE: PLEASE SEE THAT PANEL SHALL NOT | | BE LOCATED IN BATHROOM.240.24E | | | | 3)NOTE: PLEASE CORRELATE OCP FOR A/C | | UNITS WITH WHAT IS SHOWN ON MECH DETAIL. | | ONE SHOWN AS 25A OCP OTHER SHOWN AS 30A | | | | 4)NOTE: PLEASE SEE THAT SD'S ARE NOT TO | | BE LOCATED W/IN 3' OF BATHROOM DOORS. | | NFPA-72 8-1.4.2 | | | | 5)NOTE: PLEASE SEE THAT CIRCUITS ARE | | SHOWN ON PANEL W/#14AWG AND 20A OCP. | | PLEASE SEE 310.16 AND NOTES TO TABLE. | | | | 6)NOTE: PLEASE SEE THE MIN REQ'D FOR | | BATH GFI. 210.52D, 210.11.C3 , PLEASE | | SEE THAT ALL BATH GFI'S ARE BEING SHOWN | | ON ONE CIRCUIT? | | | | 7)NOTE: NOTE TO PANEL/MAIN AIC RATING IS | | SHOWN AS A/C RATING. PLEASE CORRECT. | | | | 8)NOTE: PLEASE SHOW LOAD CALCUALTIONS | | PER 220. | | | | 9)NOTE: PLEASE SEE FAC 61G15-23.002 AND | | FS 481. PLEASE SEE THAT TITLE BLOCK IS | | MISSING REQ'D LICENSE # INFORMATION. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|