Plan Review Notes For Permit 03081509 |
Permit Number |
03081509 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-11-04 00:00:00 | PROVISO: | | AS PER REVISION TO THE 2001 FBC(M) 601.4 | | EFFECTIVE JUNE 30,2003: | | EXCEPTION: | | 2. TRANSFER GRILLES SHALL USE 50 SQ INCH | | TO 100 CFM OF SUPPLY AIR WITH A 1 INCH | | UNRESTRICTED DOOR UNDERCUT.SOME OF THE | | TRANSFER GRILLES ARE INADEQUATE, PLEASE | | REVISE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|