2003-11-04 00:00:00PROVISO:
 AS PER REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30,2003:
 EXCEPTION:
 2. TRANSFER GRILLES SHALL USE 50 SQ INCH
 TO 100 CFM OF SUPPLY AIR WITH A 1 INCH
 UNRESTRICTED DOOR UNDERCUT.SOME OF THE
 TRANSFER GRILLES ARE INADEQUATE, PLEASE
 REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.