Plan Review Notes For Permit 03081509 |
Permit Number |
03081509 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-04 00:00:00 | 1) FIRE ALARM NOTES # 13 IS INCORRECT. | | DUCT SMOKE DETECTORS SHALL CAUSE A | | BUILDING ALARM NOT A SUPERVISORY SIGNAL. | | | | 2) SEPARATE PLANS REQUIRED FOR NEW | | FIRE ALARM EQUIPMENT. | | | | 3) IF EXISTING OFFICE/BEDROOMS ARE | | BEING USED FOR SLEEPING PURPOSES, THEN | | ELECTRIC POWERED SMOKE DETECTORS ARE | | REQUIRED INSIDE AND OUTSIDE OF THEM. | | PLEASE ADVISE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|