Plan Review Notes
Plan Review Notes For Permit 03081509
Permit Number 03081509
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-09-04 00:00:001) FIRE ALARM NOTES # 13 IS INCORRECT.
 DUCT SMOKE DETECTORS SHALL CAUSE A
 BUILDING ALARM NOT A SUPERVISORY SIGNAL.
  
 2) SEPARATE PLANS REQUIRED FOR NEW
 FIRE ALARM EQUIPMENT.
  
 3) IF EXISTING OFFICE/BEDROOMS ARE
 BEING USED FOR SLEEPING PURPOSES, THEN
 ELECTRIC POWERED SMOKE DETECTORS ARE
 REQUIRED INSIDE AND OUTSIDE OF THEM.
 PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910