2003-09-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY IF HEATER IS GAS
 OR ELECTRIC? ELECTRICAL RISER SHOWS
 BRANCH CIRCUIT FOR HEAT PUMP? #6`S?
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION,
 SHOWS SPA ALONG WITH POOL? PLEASE SEE
 PLAN, PLEASE CLARIFY WHERE SPA IS?
  
 3)NOTE: PLEASE SEE ATTACHED COPY OF
 FAC 61G15-23.002. PLEASE INCLUDE THE
 CERTIFICATE OF AUTHORIZATION # ONTITLE
 BLOCK AS REQ'D UNDER FS 471.
  
 PLEASE SEE PLUMB COMMENTS AS ELECTRICAL
 AND PLUMB ARE ON SAME SHEET.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  