Plan Review Notes For Permit 03081417 |
Permit Number |
03081417 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-29 00:00:00 | PROVISO: | | | | 1. BALANCE AIR RETURN - RETURN TRANSFER | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM IT'S SERVING & THE | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. | | | | 2. ATTIC ACCESS OPENING SHALL BE NO LESS | | THAN 30" X 22" AS PER 2001 FBC(M) 306.3 | | | | 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 - | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS | | LOCATED WITHIN 6 FT OF AN ATTIC | | ACCESS. | | 2. A DEVICE IS INSTALLED TO ALERT THE | | OWNER OR SHUT DOWN WHEN THE | | CONDENSATE DRAIN IS NOT WORKING | | PROPERLY. | | 4. A NOTICE IS POSTED ON THE ELECTRIC | | SERVICE PANEL INDICATING TO THE | | HOMEOWNER THAT THE AIR HANDLER IS | | LOCATED IN THE ATTIC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|