Plan Review Notes
Plan Review Notes For Permit 03081413
Permit Number 03081413
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-17 00:00:00BUILDING REVIEW CHECKLIST:
 1-SURVEY HAS INCORRECT/INCOMPLETE INFO.
 A)LEGAL DESCRIPTION: FILL IN INFORMATION
 AND THIS IS PALM BEACH COUNTY, NOT
 MARTIN COUNTY.
 B)SURVEYOR'S NOTES: NEED COMNPLETE AND
 CORRECT INFORMATION ON ITEM #3.
 **ITEM #9: REVISE ADDRESS. THIS IS WEST
 PALM BEACH, NOT PALM BEACH COUNTY.
 **ITEM #10: WPB USES MAP DATED MARCH 1ST
 1979. REVISE MAP AND PANEL # AS REQ'D.
 C)BUILDING FOOTPRINT DOESN'T MATCH
 FLOOR PLANS. REVISE AS REQUIRED.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE AIR HANDLER UNIT COMPLETE
 HANGING DETAILS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 5-PRIVACY WALL SECTION DETAIL: SPECIFY
 VERTICAL REINFORCEMENT AND ATTACHMENT
 TO CANTILEVERED FOOTING. SECTION
 104.2.1.2 CITY AMENDEMNTS TO FBC 2001.
 6-PROVIDE CALCULATIONS FOR UPLIFT LOADS
 AT REAR COVERED PORCH CONCRETE PADS.
 SEC. 1606.1.3 FBC 2001 AND SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION THRU
 BAY WINDOW AT CAFE AREA. PROVIDE
 SPECS FOR CANTILEVERED BEAM AND THE
 ATTACHMENT TO COLUMNS. ALSO, PROVIDE
 DETAIL AT INTERSECTION OF COVERED
 PORCH BEAM, CAFE BAY WINDOW BEAM AND
 LANAI BEAM. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW STEEL STRESS TO BE INCREASED.
 **NOTE: USE SIMPSON HIGH WIND-RESISTANT
 CONSTRUCTION CATALOGUE WHICH HAVE THE
 REVISED VALUES.
 9-SPECIFY WASHERS FOR GARAGE STRUCTURAL
 BUCK DETAIL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT FRONT AND
 REAR PORCHES. SPECIFY ALL MATERIALS
 AND FASTENER TYPE AND SPACING. SEE
 ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 11-PROVIDE COMPLETE INFORMATION ON TOP
 OF ENERGY CALCULATIONS FORM.
 12-STORM SHUTTERS: CLEARLY MARK ON DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO THE DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO.
 13-SITE SPECIFIC PRODUCT APPROVAL FOR
 BUTT GLAZING SYSTEM: A)PANEL TESTED
 HAS THREE PANELS. PANEL SHOWN ON PLANS
 HAS 4 PANELS. PROVIDE COMPLETE ENGINEE
 RING ANALYSIS FOR PROPOSED SYSTEM.
 SEC. 2406.1 AND 2406.2 FBC 2001.
 **NOTE: TEST DOESN'T SPECIFY EDITION
 OF ASTM E330. NEED TO USE THE CRITERIA
 SET ON ASTM E330-84 EDITION WHICH IS
 THE ONE REFERENCED IN THE FBC.
 **PROVIDE ORIGINAL SEALED, SIGNED AND
 DATED TEST REPORTS AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 **PRODUCT APPROVAL SUBMITTED IS FOR
 4500 SERIES STOREFRONT SYSTEM. PRODUCT
 APPROVAL FORM CALLS FOR 4000 SERIES.
 CLARIFY AS REQUIRED.
 **PRODUCT APPROVAL FORM DOESN;T SPECIFY
 THICKNESS FOR 1200 TYPE SILICONE.
  
 14-OWES $6.81 FOR UPDATED VALUATION.