Plan Review Notes
Plan Review Notes For Permit 03081410
Permit Number 03081410
Review Stop M
Sequence Number 1
Notes
Date Text
2003-09-03 00:00:00PROVISO:
  
 1. BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
 PLEASE NOTE ALL SUPPLY AIR INTO THE
 MASTER SUITE SHALL BE INCLUDED (EXCEPT
 FOR THE BATHROOM). 2001 FBC(M) 601.4.
  
 2. BATHROOMS SHALL HAVE A WINDOW WITH
 A MINIMUM OF 3 SQ FT OF OPEN SPACE OR
 BE MECHANICALLY VENTILATED. 2001 FBC(M)
 402.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved