Plan Review Notes For Permit 03081255 |
Permit Number |
03081255 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) PER TABLER 403.1 A DRINKING FOUNTAIN | | IS REQUIRED. ALSO SEE SEC 410.1 | | 2) SHT P0.1 DOMESTIC WATER ISOMETRIC, | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | AND MANUF. INSTALL. INSTRUCTIONS. (SEE | | PLUMBING NOTES #13). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|