Plan Review Notes
Plan Review Notes For Permit 03081255
Permit Number 03081255
Review Stop P
Sequence Number 1
Notes
Date Text
2003-09-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PER TABLER 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SEC 410.1
 2) SHT P0.1 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCTIONS. (SEE
 PLUMBING NOTES #13).
  
 REVIEW BY KEN STEVENS