2003-09-04 00:00:00 | 1) FIRE ALARM NOTES # 17 IS INCORRECT. | | ACTIVATION OF DUCT SMOKE DETECTORS | | SHALL CAUSE AN ALARM NOT A SUPERVISORY | | SIGNAL. | | | | 2) FIRE ALARM NOTES # 19 IS INCORRECT. | | FIRE ALARM CIRCUITS SHALL BE CLASS A, | | STYLE D NOT CLASS B, STYLE C. | | | | 3) SEPARATE PLANS AND PERMITS FOR | | FIRE ALARM AND FIRE SPRINKLER SYSTEM. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|