Date |
Text |
2003-09-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P0.1 DOMESTIC WATER ISOMETRIC, | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | AND MANUF. INSTALL. INSTRUCT. (SEE NOTE | | #13 OF THE PLUMING NOTES). | | 2) SUBMIT PRODUCT APPROVAL SHEETS FOR | | TOTO FIXTURES, DRINKING FOUNTAIN, AND | | LAUNDRY TUB. | | 3) 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | WHO HAVE DIFFICULTY BENDING OR STOOPING | | AT DRINKING FOUNTAIN. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|