Plan Review Notes
Plan Review Notes For Permit 03081139
Permit Number 03081139
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-23 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)BEFORE A PERMIT TO CONSTRUCT CAN
 BE ISSUED, A NOTICE OF COMMENCEMENT MUST
 BE FILED WITH THE CLERK OF COURTS.
  
 3.)AREA CALCS SHOULD SHOW EXISTING,
 PROPOSED, NEW TOTALS FOR A/C AND
 UNCONDITIONED SPACE.ADDITIONS OVER
 25% MUST COMPLY WITH FBC3401.7, 2003
 AMENDMENT.
  
 4.)TYPICAL WINDOW & DOOR ANCHOR
 DETAIL (SHEET 1) TO COMPLY WITH
 FBC1707.4.4.2.
  
 5.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.SIGN OWNER/AGENT LINE AS WELL AS
 PREPARER LINE OF ENERGY CALC.
  
 6.)TITLE BLOCK REQUIRED FOR ENGINEER,
 FAC 61G15-23, TO INCLUDE NAME, ADDRESS,
 AND NUMBER.
  
 7.)ADDITIONAL FEES DUE, $8.68, SEE
 ATTACHED BZ231209.
  
 8.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 9.)THE CONNECTOR "SIMPSON RT1818" IS
 NOT IN THE 2003 CATALOG (DOOR/WINDOW
 HEADER, SHEET 2).
  
 10.) FIRESTOP REQUIRED, FBC705.3.