Plan Review Notes
Plan Review Notes For Permit 03081117
Permit Number 03081117
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/
 PANELS/ PLANS. PLEASE SEE RISER SHOWS
 A PANEL L2F? PLEASE CLARIFY WHERE THIS
 IS ON PLANS AND PANEL SCHEDULE.215.5
  
 2)NOTE: PLEASE PROVIDE PANEL SCHEDULE
 FOR L2A, PLEASE ALSO NOTE:
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. 215.3,230.42 ETC
  
  
 PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWERS THAT MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS,
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  