Plan Review Notes
Plan Review Notes For Permit 03081061
Permit Number 03081061
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-12 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 THE INTERNAL PRESSURE COEFFICIENT FOR AN
 ENCLOSED STRUCTURE IS + OR - 0.18.
 SPECIFY THIS INFORMATION ON THE PLAN FOR
 THE ADDITION. SOME OF THIS IS ON THE
 PLANS UNDER ROOF NOTES, HOWEVER ALL OF
 THE ADDITION IS REQUIRED TO COMPLY.
  
 4) SPECIFY THE POSITIVE AND NEGATIVE
 WIND LOAD PRESSURES FOR THE WINDOW AND
 DOOR OPENINGS IN THE ADDITION.
  
 5) ON SHEET S-2 SECTION B-B IS INDICATED
 ON THE FOUNDATION PLAN AND THE DETAIL IS
 MARKED G-G. PLEASE CORRECT. SPECIFY THE
 SPACING OF THE DOWELS SHOWEN IN THE
 DETAIL.
  
 6) SPECIFY THE LENGTH OF THE 1/2" BOLT
 IN THE DETAIL ON S-2. THE SPACING OF THE
 BOLTS IS 4 FT. ON CENTER ON S-2 AND 2 FT
 ON CENTER ON THE SLOPE AND FLAT ROOF
 SECTIONS ON D-1. THE FLAT ROOF SECTION
 SPECS. A 6" EMBED AND THE SLOPED ROOF
 SECTION HAS 4" EMBED FOR BOLTS. PLEASE
 CLARIFY.
  
 7) SPECIFY THE SIZE OF THE NEW BATHROOM
 DOOR. FBC 11-43.23.2 REQUIRES ONE BATH
 ROOM WITH AT LEAST A 29" CLEAR OPENING.
  
 8) THE RTPGA STRAPS SPECIFIED IN THE
 ANCHOR SCHEDULE ON R-1 ARE NOT LISTED IN
 THE 2003 USP CATALOG. PLEASE UPDATE.
  
 9) THE WALL SECTIONS ON D-1 SPECIFY 5/8"
 STUCCO. ASTM C 926 REQUIRES STUCCO OVER
 METAL LATH (VERTICAL) TO BE 7/8" THICK.
 SEE FBC 2504.2.1.
  
 10) UPDATE THE STRAPS AND STUD PLATE
 TIES TO CONNECTORS LISTED IN CURRENT
 MANUFACTURERS' CATALOGS. SEE NOTES ON
 THE PLAN.
  
 11) PLEASE REVIEW DETAILS ON D-1 AND
 CLARIFY THE SIZE OF THE FRAME WALLS.
 SPECIFY R-11 INSULATION FOR 2X4 WALLS
 AND R-19 FOR 2X6 WALLS. USP SPT 4 PLATE
 CONNECTORS ARE FOR 2X4 WALLS AND SPT 6
 ARE FOR 2X6 WALLS.
  
 12) THE PLANS SPECIFY R-30 INSULATION IN
 THE SINGLE ASSEMBLY ENCLOSED CEILING.
 THIS WILL INTERFERE WITH VENTILATION.
 THE CODE WILL ALLOW R-19 FOR THIS
 APPLICATION. INDICATE THE APPROPRIATE
 INSULATION ON THE PLAN AND ON THE ENERGY
 FORM AS REQUIRED BY FBC 11-604.1.
  
 13) NOTE 4 ON T-1 STATES THAT THE
 EXISTING WALLS ARE CBC AND THE PLANS
 INDICATE WOOD FRAME WALLS. PLEASE
 CLARIFY.
  
 14) PROVIDE DETAILS OF THE STRUCTURAL
 REPAIRS THAT WILL BE MADE TO THE EXIST-
 ING BEARING WALLS THAT WERE DAMAGED.
 REVISE NOTE ON T-1 TO SPECIFY THAT THE
 ENGINEER IS RESPONSIBLE FOR THE REPAIRS
 TO THE EXISTING STRUCTURE AND THE NEW
 ADDITION.
  
 15) THE INFORMATION ON THE ENERGY FORM
 IS INCORRECT. PLEASE CORRECT AND SUBMIT
 TWO COPIES.
  
 16) THE PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOWS IS ILLEGIBLE. SUBMIT
 TWO CLEAR READABLE COPIES.
  
 17) THE PRODUCT APPROVALS FOR THE FRENCH
 DOORS ARE NOT ACCEPTABLE. THE ACCEPTANCE
 NUMBER ON THE COVER SHEET DOES NOT MATCH
 THE ONE ON THE DRAWINGS AND PAGES ARE
 MISSING FROM THE NOA. SUBMIT TWO
 COMPLETE AND READABLE PRODUCT APPROVALS
 FOR THE DOUBLE OUTSWING FRENCH DOORS.
  
 18) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING MATERIAL.
  
 19) SUBMIT TWO COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE MOUNTING TYPE,
 ANCHOR TYPE AND ANCHOR SPACING THAT WILL
 BE USED.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved