Plan Review Notes For Permit 03081003 |
Permit Number |
03081003 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-21 00:00:00 | DENIED: | | | | 1. PLEASE PROVIDE INFORMATION AS TO THE | | TONNAGE OF THE EXISTING EQUIPMENT. | | | | 2. PROVIDE THE ADDITIONAL SQUARE FOOTAGE | | OF THE SPACE TO CONDITIONED. | | | | 3. AS PER 2001 FBC(M) 104.2.1.1, TWO | | COPIES ARE TO BE SUBMITTED FOR REVIEW. | | | | 4. PROVIDE DUCT AND GRILLE SIZES. | | | | 5. PROVIDE REVISED OUTSIDE AIR CALCS AS | | PER 2001 FBC(M) TABLE 403.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|