2003-09-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) LAUNDRY SINK SHALL CONNECT DOWN-
 STREAM OF THE BATHROOM FIXTURES. SECTION
 909.1
 B) WASH MACHINE SHALL NOT DRAIN PAST
 THE TUB. SECTION 712.3.5
 C) BIDET IN MASTER BATHROOM NOT VENTED.
 D) SECOND LAV IN MASTER BATH NOT SHOWN
 ON SANT. RISER.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS.
  