Plan Review Notes
Plan Review Notes For Permit 03080864
Permit Number 03080864
Review Stop B
Sequence Number 1
Notes
Date Text
2003-09-02 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE SURVEY IS THE REVERSE OF THE
 ARCHITECTURAL PLANS. PLEASE CORRECT.
  
 4) THE DOOR TO THE TOILET IN THE MASTER
 BATH DOES NOT COMPLY WITH THE 29" CLEAR
 OPENING REQUIRED BY FBC 11-4.22.2.
  
 5) THE DIMENSIONS FOR THE STAIR RISERS
 AND TREADS ON A-2 DOES NOT CORRESPOND
 WITH DETAILS 12 AND 13 ON A-8. THE
 INTERMEDIATE RAILS ON THE STAIRS ARE
 REQUIRED TO REJECT A 4" SPHERE PER FBC
 1015.3.
  
 6) REVISE DETAIL 4 ON A-8. STUCCO ON
 VERTICAL METAL BASE IS REQUIRED TO BE
 7/8" THICK PER FBC 2504.2.1 AND ASTM C
 926.
  
 7) THE TWO STORY WALL SECTION ON A-6
 SPECIFIES AN 18" WIDE FOOTING AND THE
 FOOTING SCHEDULE ON A-1 REQUIRES A 20"
 WIDE FOOTING. PLEASE CORRECT.
  
 8) THE COLUMN IS NOT SPECIFIED AT THE
 F10 PAD ON SHEET A1.
  
 9) REVISE THE BUCK DETAIL ON A-8. THE
 FRAMES ARE REQUIRED TO BE FASTENED
 THROUGH THE 1X BUCKS INTO THE SUBSTRATE
 PER FBC 1707.4.4.2.
  
 10) SUBMIT AN INSTALLATION SCHEDULE AND
 KEY PLAN FOR THE STORM PANELS.
  
 11) REVISE THE STUCCO NOTES ON SECTION
 A-A ON A-6. HIGH RIB METAL LATH IS
 REQUIRED TO BE FASTENED AT EVERY RIB
 (4"O.C.) PER ASTM C 1063. SEE FBC
 2504.2.2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714