2003-12-17 00:00:00 | *****CORRECTIONS****** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEPARATE PERMITS REQUIRED. |
| |
| 2.)ADDITIONAL FEES DUE, $43.06, |
| BZ WAS IN PACKAGE BUT IS NOW GONE. |
| |
| 3.)A NOTICE OF COMMENCMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 4.)SEE PREVIOUS LISTS, 3RD TIME ON |
| THIS CORRECTION, PROVIDE WIND |
| INFORMATION ON THE PLAN FBC1606.1.7 |
| INCLUDING COMPONENTS AND CLADDING |
| (DESIGN PRESSURE FOR DOORS). |
| |
| 5.)SEE PREVIOUS LISTS, 3RD TIME ON |
| THIS CORRECTION, MTSM16 NAILING |
| CONFLICTS WITH CATALOG.ADDRESS. |
| |
| 6.)SEE PREVIOUS LISTS, 3RD TIME, |
| REGARDING PLYWOOD SOFFIT AND CEILING, |
| FBC2303.3. |
| |
| 7.)SEE PREVIOUS LISTS IN REGARDS |
| TO LSTA18, NAILING CONFLICTS WITH |
| CATALOG.3RD TIME |
| |
| 8.)THE ROOM DESIGNATION FOR EXISTING |
| ROOMS WAS REMOVED ON THE NEW DRAWING. |
| THE ROOM LEADING FROM THE HOUSE TO THE |
| STORAGE MUST BE SHOWN ON THE PLAN. |
| |
| 9.)THE SITE PLAN WHICH WAS NOT ON THE |
| PLAN PREVIOUSLY BUT IS NOW ON THE NEW |
| DRAWINGS CONFLICTS WITH THE APPROVED |
| ZONING.THE ADDITION IS NOW SHOWN ON |
| THE OTHER SIDE OF THE BUILDING.ISN'T |
| THIS ALREADY BUILT AND CLEARLY SHOWN ON |
| THE SURVEY?CLARIFY. |
| |
| 10.)SEE THE FIRST LIST IN REGARDS |
| TO STUCCO, VERTICAL APPLICATION OVER |
| WIRE LATH IS TO BE 3 COAT 7/8" |
| FBC2504.2.2.SECOND CORRECTION. |
| |
| 11.)SEE THE PREVIOUS TWO LISTS. APPLY |
| FOR AN A/C PERMIT. |
| |
| 12.)AS PER FS553, A 4X PLAN REVIEW IS |
| BEING CHARGED.SEE ATTACHED.THIS WILL |
| BE CHARGED EVERY TIME THIS IS |
| RESUBMITTED AND THE CORRECTIONS HAVE NOT |
| BEEN MADE. |