2003-10-20 00:00:00 | *****CORRECTIONS***** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEPARATE PERMITS REQUIRED. |
| |
| 2.)SEE PREVIOUS LIST, TITLE BLOCK |
| REQUIRED FOR ENGINEER FAC61G15-23.002(2) |
| |
| 3.)ADDITIONAL FEES DUE, ADJUSTED |
| VALUE AND RADON, $43.06, BZ231382. |
| |
| 4.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 5.)SEE PREVIOUS LIST, ITEM #7, PROVIDE |
| WIND INFORMATION ON THE PLAN FBC1606.1.7 |
| COMPONENTS AND CLADDING (NO DESIGN |
| PRESSURE FOR DOORS). |
| |
| 6.)CHANGES MADE TO THE PLAN MUST BE |
| CLOUDED AND INITIALED BY THE ENGINEER. |
| DO NOT WHITE OUT THE PLAN. |
| |
| 7.)SEE PREVIOUS CORRECTION #10.MTS |
| WAS CHANGED TO MTSM16, BUT THE FASTENERS |
| WERE NOT CHANGED AND CONFLICT WITH THE |
| CATALOG DETAIL YOU PROVIDED. |
| |
| 8.) SEE PREVIOUS LIST #13, REGARDING |
| PLYWOOD SOFFIT AND CEILING, SURFACES |
| EXPOSED TO THE WEATHER SHALL HAVE AN |
| APPROVED BARRIER TO PROTECT THE |
| STRUCTURAL FRAME FBC2303.3.A NOTE WAS |
| MADE ON THE CORRECTION LIST, 1/2 PWT, |
| PLYWOOD TREATED?THIS NEEDS TO BE ON |
| THE PLAN, NOT A NOTE ON THE CORRECTION |
| LIST. |
| |
| 9.)THE DETAIL PROVIDED FOR LSTA18 |
| SHOWS A FLOOR TO FLOOR INSTALLATION; |
| THIS DETAIL FOR AN APPLICATION YOU ARE |
| NOT USING IS NOT NECESSARY.THE |
| CORRECTION WAS RELATED TO THE NUMBER OF |
| NAILS ORIGINALLY SPECIFIED. |
| |
| 10.) SEE PREVIOUS LIST #12.PROVIDE AN |
| A/C PERMIT NUMBER. |
| |
| 11.) SEE ATTACHED NOTE REGARDING FS |
| 553.80(2)(B). |