2003-09-20 00:00:00 | ******CORRECTION******** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| 1.)SEPARATE PERMITS REQUIRED. |
| |
| 2.)TITLE BLOCK REQUIRED FOR ENGINEER; |
| FAC61G15-23.002(2). |
| |
| 3.)ADDITIONAL FEES DUE; ADJUSTED VALUE |
| AND RADON ($367.96).BZ231378 |
| |
| 4.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED AND THE RECEIPT ATTACHED TO THE |
| APPLICATION. |
| |
| 5.)IMPACT PROTECTION REQUIED FOR |
| GLAZING; FBC1606.1.4.PROVIDE TWO |
| COPIES OF PRODUCT APPROVALS. |
| |
| 6.)STUCCO IS REQUIRED TO BE 3-COAT |
| (7/8") FOR VERTICAL APPLICATION ON |
| WIRE LATH; FBC2504.2.2, ASTMC1063. |
| |
| 7.)PROVIDE WIND INFORMATION ON THE |
| PLAN, FBC1606.1.7. |
| |
| 8.)CLARIFY - DOORS ARE SHOWN LEADING |
| FROM THE KITCHEN TO THE NEW AREA.ARE |
| THESE DOORS EXISTING? |
| |
| 9.)A TOTAL OF FIVE DOORS ARE SHOWN |
| ON THE PLAN.ARE ALL OF THEM GLAZED? |
| IF NOT, PROVIDE 2 COPIES OF PRODUCT |
| APPROVALS FOR THE DOORS INSTALLED. |
| THE PLAN SHOWS METAL DOORS. |
| |
| 10.) THE ATTACHMENT SPECIFIED FOR MTS12 |
| AND LSTA18 CONFLICT WITH THE SIMPSON |
| 2003 CATALOG. |
| |
| 11.) MTS12 IS A WOOD-TO-WOOD CONNECTOR. |
| YOU ARE USING IT IN A WOOD-TO-MASONRY |
| APPLICATION.EITHER SPECIFY A DIFFERENT |
| CONNECTOR, OR GET CONFIRMATION FROM THE |
| MANUFACTURER THAT YOU CAN USE IT IN THIS |
| APPLICATION. |
| |
| 12.)APPLY FOR AN A/C PERMIT.NEW |
| A/C IS SHOWN ON THE SURVEY, BUT I CANNOT |
| FIND A RECORD OF AN A/C PERMIT IN OUR |
| RECORDS. |
| |
| 13.)REGARDING THE PLYWOOD SOFFIT AND |
| PLYWOOD CEILING, SURFACES EXPOSED TO THE |
| WEATHER SHALL HAVE AN APPROVED BARRIER |
| TO PROTECT STRUCTURAL FRAME, FBC2303.3. |
| |
| 14.)CLEARANCE BETWEEN WOOD SIDING |
| AND EARTH SHALL NOT BE LESS THAN 6", |
| FBC2304.2.5. |
| |
| 15.)BOTTOM OF FOOTER REQUIRED TO BE |
| MINIMUM OF 12" BELOW GRADE, FBC1804.1.3. |
| |
| 16.)MTS12 IS A WOOD-TO-WOOD CONNECTOR, |
| WHICH YOU ARE USING IN A WOOD-TO-MASONRY |
| APPLICATION.EITHER SPECIFY A DIFFERENT |
| ATTACHMENT OR GET CONFIRMATION FROM THE |
| MANUFACTURER THAT YOU CAN USE IT IN THIS |
| APPLICATION. |
| |
| 17.)REGARDING THE PLYWOOD SOFFIT AND |
| THE PLYWOOD CEILING (PORCH), SURFACES |
| EXPOSED TO THE WEATHER SHALL HAVE AN |
| APPROVED BARRIER TO PROTECT THE |
| STRUCTURAL FRAME, FBC2303.3. |
| |
| 18.)CLEARANCE BETWEEN WOOD SIDING AND |
| THE EARTH SHALL NOT BE LESS THAN 6", FBC |
| 2304.2.5. |