1 |
|
Notes |
Date |
Text |
2003-08-15 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | THERE ARE NO ELECTRICAL PLANS | | SUBMITTED, SCOPE OF WORK IS NOT CLEAR. | | IF A NEW SERVICE IS BEING INSTALLED | | PROVIDE RISER DIAGRAM AND LOAD CALCS | | FOR EXISTING AND ALL LOADS BEING | | ADDED.ALSO SHOW CONDUIT & WIRE SIZE AND | | ROUTING FOR NEW EQUIPMENT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | E-MAIL [email protected]. |
|