Plan Review Notes
Plan Review Notes For Permit 03080731
Permit Number 03080731
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-25 00:00:00THE STRUCTURAL CALCULATIONS SIGNED AND
 SEALED BY THOMAS TWOMEY, PE DATED
 8/13/03 ARE NOT ACCEPTABLE.
  
 THE CALCULATIONS USE THE
 NOMINAL SIZE OF THE LUMBER 3X12 RATHER
 THAN THE ACTUAL 2 3/4"X11".THERE IS NO
 FACTOR FOR DURATION OR AN INVESTIGATION
 FOR DEFLECTION.IS THE PLASTER AND WOOD
 LATH CEILING INCLUDED IN THE MISC. 5
 PSF?OTHER COLLATERAL LOADS SUSPENDED
 BELOW, IE MECHANICAL AND SPRINKLER
 SYSTEMS?