Plan Review Notes
Plan Review Notes For Permit 03080698
Permit Number 03080698
Review Stop P
Sequence Number 1
Notes
Date Text
2003-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-1 TABLE 403.1 REQUIRES A DRINK-
 ING FOUNTAIN. (ALSO SEE SECTION 410.1)
 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 LOUNGE SINK. 11-24.5
 3) SHT P-2 AN RPZ BACKFLOW IS REQUIRED.
 SECTION 608.13.2
 4) SHT P-1 SHOWS RELIEF VALVE DISCHARGE
 LINE (P&T) AND THE PAN DRAIN RUNNING
 OVERHEAD. PLEASE CLAIRFY/SECTION 504.7.1
 5) PROVIDE EXPLAINATION OF HOW THE LAB,
 EXAMINATION ROOMS ECT WILL BE CLEANED
 WITHOUT A SERVICE SINK. SECTION 403.1
  
 REVIEW BY KEN STEVENS