Plan Review Notes
Plan Review Notes For Permit 03080695
Permit Number 03080695
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-08-14 00:00:00UNDER THE FIRE ALARM SEQUENCE OF
 OPERATION. THE ACTIVATIN OF ANY HVAC
 DUCT DETECTOR SHALL ANNUNCIATE AT THE
 MAIN FIRE ALARM PANEL AS AN ALARM
 CONDITION SHOWING ZONE IN ALARM. AND
 TRANSMIT AN ALARM TO A U.L. LISTED
 CENTRAL STATION PER THE WEST PALM BEACH
 FIRE MARSHAL OFFICE. NOT A SUPERVISORY.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910