Plan Review Notes
Plan Review Notes For Permit 03080678
Permit Number 03080678
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-18 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY SERVICE, NEW,
 EXISTING?
 IF NEW SUBMIT AIC RATING FOR NEW MCB.
 110.9/215.5
  
 2)NOTE: PLEASE SEE RISER DAIGRAM, SHOWS
 SUB-FEED TO ANOTHER PANEL? 3-3/0`S ?
 PLEASE SEE PANEL SCHEDULE SUBMITTED,
 DOES NOT SHOW THIS? PLEASE CLARIFY.
  
 3)NOTE: PLEASE SEE OCP SHOWN FOR AHU,
 10KW W/ 30A OCP. PLEASE SEE 424.3B
  
 4)NOTE: PLEASE SEE 220.16 FOR MIN LOAD
 FOR WASHER CIRCUIT. 1500VA
  
 5)NOTE: PLEASE SEE 220.18 FOR MIN LOAD
 FOR DRYER.
  
 6)NOTE: PLEASE NOTE, RISER DIAGRAM SHOWS
 GEC TO FOOTER STEEL, THIS IS NOT REQ'D
 WHEN THERE IS AN EXISTING BLDG, HOWEVER
 IF SHOWN ON PLANS, THEN IT WILL BE REQ'D
 TO BE INSTALLED. 250.50.
  
 7)NOTE: PLEASE MOVE SD IN MAIN RM TO BE
 IN THEN VICINITY OUTSIDE BEDRM DOOR.
 NFPA-72 8-1.4.2
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPT
 REQ'D FRONT OF DWELLING. 210.52E
  
 9)NOTE: PLEASE SEE ONLY TWO SM APPL
 FIGURED IN LOAD CALCS AND THREE SHOWN
 ON PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]