Plan Review Notes For Permit 03080678 |
Permit Number |
03080678 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-18 00:00:00 | *********** UNSAT **************** | | | | 1)NOTE: PLEASE CLARIFY SERVICE, NEW, | | EXISTING? | | IF NEW SUBMIT AIC RATING FOR NEW MCB. | | 110.9/215.5 | | | | 2)NOTE: PLEASE SEE RISER DAIGRAM, SHOWS | | SUB-FEED TO ANOTHER PANEL? 3-3/0`S ? | | PLEASE SEE PANEL SCHEDULE SUBMITTED, | | DOES NOT SHOW THIS? PLEASE CLARIFY. | | | | 3)NOTE: PLEASE SEE OCP SHOWN FOR AHU, | | 10KW W/ 30A OCP. PLEASE SEE 424.3B | | | | 4)NOTE: PLEASE SEE 220.16 FOR MIN LOAD | | FOR WASHER CIRCUIT. 1500VA | | | | 5)NOTE: PLEASE SEE 220.18 FOR MIN LOAD | | FOR DRYER. | | | | 6)NOTE: PLEASE NOTE, RISER DIAGRAM SHOWS | | GEC TO FOOTER STEEL, THIS IS NOT REQ'D | | WHEN THERE IS AN EXISTING BLDG, HOWEVER | | IF SHOWN ON PLANS, THEN IT WILL BE REQ'D | | TO BE INSTALLED. 250.50. | | | | 7)NOTE: PLEASE MOVE SD IN MAIN RM TO BE | | IN THEN VICINITY OUTSIDE BEDRM DOOR. | | NFPA-72 8-1.4.2 | | | | 8)NOTE: PLEASE SEE MISSING GFI RECEPT | | REQ'D FRONT OF DWELLING. 210.52E | | | | 9)NOTE: PLEASE SEE ONLY TWO SM APPL | | FIGURED IN LOAD CALCS AND THREE SHOWN | | ON PANEL. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|