Date |
Text |
2003-09-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOORS WITH SIDELITE ASSEMBLY AS SHOWN |
| ON PLANS. |
| 3-WINDOW MULLION PRODUCT APPROVAL AND |
| LETTER EXTENDING EXPIRATION DATEARE |
| EXPIRED. RESUBMIT AS REQUIRED. |
| 4-PROVIDE PRODUCT APPROVAL FOR FIXED |
| WINDOW ABOVE FAMILY ROOM. SEE PLANS |
| FOR SIZE. |
| 5-PROVIDE COMPLETE SOIL TEST REPORT WITH |
| SOIL BEARING CAPACITY. SOIL PREP. AND |
| FOOTING RECOMMENDATIONS. SECTION |
| 1804.1.7 CITY AMENDMENTS TO FBC 2001. |
| 6-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS. SEC. 2405.2 FBC 2001. |
| 7-MISSING SOME CONNECTORS. SEE ROOF PLAN |
| AND SPECIFY THEM AS REQUIRED. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 8-PROVIDE DETAIL AT CONNECTION OF GABLE |
| END TRUSS TO GABLE END CONCRETE BLOCK |
| WALL AT REAR PORCH. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 9-CLARIFY DETAIL 5/A6. SEE ROOF PLAN. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |