Notes
Date Text
2004-03-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUPPLY THE FOLLOWING
 INFORMATION REGARDING THE GENERATOR.
 A) TYPE OF FUEL USED.
 B) WIRING DIAGRAM OR SCHEMATIC SHOWING
 THAT THE GENERATOR WILL NOT
 BACKFEED FPL THROUGH THE TRANSFER
 SWITCH.
 C) THE TRANSFER SWITCH APPEARS TO BE
 BEHIND THE GENERATOR AND NOT IN
 COMPLIANCE WITH 110.26.
 D) HOW IS THE EXHAUST FROM THE GENER-
 ATOR BEING VENTED?
  
 2} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 3} THE DEMAND ON PANEL "A" IS TOO LARGE
 FOR THE 200 AMP PANEL.PLEASE
 RECALCULATE OR MOVE LOADS. SHOW
 CALCULATIONS PER 215.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  