Plan Review Notes For Permit 03080509 |
Permit Number |
03080509 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-03-01 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUPPLY THE FOLLOWING | | INFORMATION REGARDING THE GENERATOR. | | A) TYPE OF FUEL USED. | | B) WIRING DIAGRAM OR SCHEMATIC SHOWING | | THAT THE GENERATOR WILL NOT | | BACKFEED FPL THROUGH THE TRANSFER | | SWITCH. | | C) THE TRANSFER SWITCH APPEARS TO BE | | BEHIND THE GENERATOR AND NOT IN | | COMPLIANCE WITH 110.26. | | D) HOW IS THE EXHAUST FROM THE GENER- | | ATOR BEING VENTED? | | | | 2} PLEASE NOTE, ALL PLANS DRAWN | | BY AN ARCHITECT/ENGINEER CONTAIN- | | -ING A TITLE BLOCK: MUST BE SIGNED, | | DATED AND SEALD BY THAT ARCH/ENG. | | PER FS 481.221 471.025 | | FAC 61G15-23.002, 61G1-16.004 | | | | 3} THE DEMAND ON PANEL "A" IS TOO LARGE | | FOR THE 200 AMP PANEL.PLEASE | | RECALCULATE OR MOVE LOADS. SHOW | | CALCULATIONS PER 215.5 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|