2003-08-21 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| |
| 1} THE METER IS NOT RATED FOR 400 AMPS. |
| |
| 2} THE SERVICE CONDUCTORS ARE NOT RATED |
| FOR 200 AMPS.SEE 310.15(B)(6). |
| |
| 3} THE GROUNDING ELECTRODE CONDUCTOR IS |
| NOT IN COMPLIANCE WITH 250.66,1/0 MIN. |
| |
| 4} PANEL "A" IS SHOWN AS 200 AMPS ON |
| THJE RISER AND 150 AMPS ON THE |
| SCHEDULE,PLEASE CORRELATE. |
| |
| 5} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE PER212.12 |
| |
| 6} PLEASE SHOW THE LOCATION OF THE |
| DISCONNECTS,SHOWN ON THE RISER,ON THE |
| PLAN. |
| |
| 7} THE GARAGE RECEPTACLES MUST COMPLY |
| WITH 210.8.(A)(2). |
| |
| 8} NOTE THAT ALL KITCHEN COUNTERTOP |
| RECEPTACLES MUST COMPLY WITH |
| 210.8(A)(6). |
| |
| 9} PLEASE NOTE KITCHEN COUNTER- |
| -SPACE RECEPT SPACING SHALL MEET ART; |
| 210-52C 1,2,3,4,AND 5. |
| |
| 10} PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52.SEE |
| REVIEWED SET. |
| |
| 11} THE POWDER ROOM REQUIRES AN OUTLET |
| TO COMPLY WITH 210.52(D). |
| |
| 12} PLEASE SEE THAT THE PLACEMENT OF |
| THESMOKE DETECTORS COMPLY WITH THE |
| INTENT |
| OF 8-1.4.1.6 NFPA-72(1999). |
| |
| 13} PLEASE NOTE THAT ALL PLANS |
| DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| ING A TITLE BLOCK, MUST BE SIGNED, |
| DATEDAND SEALED BY THE ARCH/ENGINEER OF |
| RECORD. PER FS/FAC 481.221 & 471.025 |
| |
| AFTER CORRECTIONS TO COMMENTS ARE MADE, |
| PLEASE RESUBMIT FOR REVIEW AND PROVIDE |
| THE OLD SHEETS TO FACILITATE THE REVIEW. |
| |
| IF THERE AREANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |