Plan Review Notes
Plan Review Notes For Permit 03080509
Permit Number 03080509
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 1} THE METER IS NOT RATED FOR 400 AMPS.
  
 2} THE SERVICE CONDUCTORS ARE NOT RATED
 FOR 200 AMPS.SEE 310.15(B)(6).
  
 3} THE GROUNDING ELECTRODE CONDUCTOR IS
 NOT IN COMPLIANCE WITH 250.66,1/0 MIN.
  
 4} PANEL "A" IS SHOWN AS 200 AMPS ON
 THJE RISER AND 150 AMPS ON THE
 SCHEDULE,PLEASE CORRELATE.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER212.12
  
 6} PLEASE SHOW THE LOCATION OF THE
 DISCONNECTS,SHOWN ON THE RISER,ON THE
 PLAN.
  
 7} THE GARAGE RECEPTACLES MUST COMPLY
 WITH 210.8.(A)(2).
  
 8} NOTE THAT ALL KITCHEN COUNTERTOP
 RECEPTACLES MUST COMPLY WITH
 210.8(A)(6).
  
 9} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 10} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.SEE
 REVIEWED SET.
  
 11} THE POWDER ROOM REQUIRES AN OUTLET
 TO COMPLY WITH 210.52(D).
  
 12} PLEASE SEE THAT THE PLACEMENT OF
 THESMOKE DETECTORS COMPLY WITH THE
 INTENT
 OF 8-1.4.1.6 NFPA-72(1999).
  
 13} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 AFTER CORRECTIONS TO COMMENTS ARE MADE,
 PLEASE RESUBMIT FOR REVIEW AND PROVIDE
 THE OLD SHEETS TO FACILITATE THE REVIEW.
  
 IF THERE AREANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718