Plan Review Notes For Permit 03080370 |
Permit Number |
03080370 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-09-29 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-REVISE WINDOW AND DOOR BUCK DETAILS | | TO COMPLY WITH SECTION 1707.4.4.2 FBC. | | NEED FULL WIDTH BUCK. | | 3-CLARIFY/REVISE DETAIL 16/A-8. HOW ARE | | 2X8 STUDS GOING TO BE NAILED TOGETHER | | WITH 10D COMMON NAILS. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 4-SPECIFY FIREBLOCKING MATERIAL AND | | LOCATION FOR FIREBLOCKING AT STAIRS. | | ALSO, PROVIDE GENERAL SPECIFICATIONS/ | | NOTES FOR FIREBLOCKING @ ALL CONCEALED | | SPACES. SEE SECTION 2305.1 FBC 2001. | | 5-DETAIL 4/A-8. CLARIFY SIZE OF STUDS & | | CONNECTORS. THEY DON'T MATCH. REVISE | | AS REQUIRED. |
|