Plan Review Notes
Plan Review Notes For Permit 03080370
Permit Number 03080370
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-29 00:00:00BUILDING CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE GABLE END TRUSS
 DETAIL SHOWING COMPLIANCE WITH SECTION
 2313.4 FBC 2001. SPECIFY STRUCTURAL
 CONTINUITY AT POINTS OF LATERAL
 SUPPORTS. SPECIFY ALL FASTENERS AND
 FRAMING MEMBERS.
 **NOTE: NEED TWO DETAILS SINCE THERE
 ARE TWO DIFFERENT GABLE END TYPES.
 SEE ELEVATIONS.
 4-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T
 ALLOW THE STEEL STRESS INCREASE.
 SEE SIMPSON HIGH WIND-RESISTANT
 CONSTRUCTION CATALOGUE, WHICH IS THE
 ONLY SIMPSON CATALOGUE THAT'S UPDATED.
 **ALSO, SOME CONNECTORS SPECIFIED ON
 THE TRUSS ANCHOR SCHEDULE SHOW HIGHER
 UPLIFT VALUES THAN SHOWN ON CATALOGUE.
 REVISE AS REQ'D OR PROVIDE ENGINEERING
 CALCULATIONS FOR HIGHER VALUES.
 SEE NUMBER OF NAILS SPECIFIED, ETC.
 5-REVISE DOORS/WINDOWS BUCK DETAILS TO
 COMPLY WITH SECTION 1707.4.4.2 FBC.
 6-SHEET A-1: REVISE NOTE #2 FOR CONCRETE
 SEE SEC. 1901 FBC 2001 FOR PROPER
 ACI REFERENCE.
 **CLARIFY FOOTING FOR REAR PORCH. SEE
 PLAN.
 7-SHEET A-2: A)GLASS BLOCK AT BUTH TUB/
 SHOWER AREAS TO BE SAFETY GLASS OR
 TO HAVE 0.25" MIN. FACE THICKNESS.
 SEC. 2405.2 FBC 2001. SPECIFY WHICH
 ONE IS GOING TO BE.
 B)REVISE MINIMUM SIZE OF ATTIC ACCESS.
 SEE SEC. 2309.6 FBC 2001.
 C)WINDOW AT BEDROOM #2 DOESN'T COMPLY
 WITH SEC. 1005.4.3 FBC 2001.
 D)MASTER BEDROOM TO HAVE DOOR OPENING
 AT WATER CLOSET TO ALLOW 29" MINIMUM
 CLEAR OPENING. SEC 11 OF CHAPTER 11
 FBC 2001.
 E)DEN ROOM DOESN'T HAVE EGRESS WINDOWS.
 PROVIDE EGRESS WINDOW OR VISIBLE WRITE
 UNDER THE DEN WORD: "THIS ROOM IS NOT
 TO BE USED FOR SLEEPING PURPOSES
 BECAUSE THERE IS NOT EGRESS OPENING"
  
 8-SHEET A/5A AND A/5B: A)REVISE ROOF
 ZONES KEY PLAN. GABLE END IS ON THE
 ROOF ZONE 3. SEE SEC. 2306 OF CITY
 AMENDMENTS TO FBC 2001.
 B)REVISE/CLARIFY DESIGN PARAMETERS.
 INTERNAL PRESSURE COEFFICENT SHALL BE
 CALCULATED FOR NEGATIVE AND POSITIVE.
 SEE ASCE 7-98.
 C)SOIL BEARING PRESSURE TO BE IN PSF,
 NOT PSI.
 D)ROOF SHEAR DIAPHRAGM SCHEDULE: NEED 8D
 RING SHANK NAIL AT ZONE #3. SEE SECT'N
 2306 CITY AMENDMENTS TO FBC 2001.
 F)REVISE ATTIC SIZE. SEC. 2309.6 FBC.
 G)SPECIFY ALL CONNECTORS FOR SHEARWALL
 SEGMENTS AND CORNERS AS SPECIFIED ON
 SHEET A-9.
  
 9-SHEET A-6: A)HEADER CONSTRUCTION AT
 ENTRY DOOR IS NOT CLEAR. SEE BUILDING
 SECTION A-A AND DETAIL 16/A-8.
 B)ATTIC VENTILATION IS FOR ENTIRE ROOF
 NOT FOR LIVING AREA ONLY. REVISE NOTES
 ON WALL SECTIONS.
 C)REVISE THICKNESS OF VAPOR BARRIER. SEE
 SEC. 1909.2 FBC 2001. REVISE NOTES ON
 WALL SECTIONS.
 D)ZERO LOT LINE WALL NEEDS ONE HOUR FIRE
 RATED ASSEMBLY WALL FROM FOOTING TO
 ROOF AND PROTECTED FROM INTERIOR AND
 EXTERIOR AS REQUIRED BY TABLE 600 FOOT
 NOTE I. NEED DETAIL/SPECS FOR FIRE
 RATED ASSEMBLY AT SECOND FLOOR AT
 TRANSITION OF CONCRETE BLOCK TO FRAMED
 WALL.
  
 10-SHEET A-8: A)DETAIL 2/A-8: UPDATE
 SEMCO CONNECTOR.
 **NEED 7/8" MIN. STUCCO. ASTM C-926.
 **SPECIFY STUD CONNECTOR TO GIRDER TRUSS
 **SAME COMMENTS FOR DETAIL 7/A-8.
 B)STAIR DETAILS: DETAIL 12/A-8 & 13/A-8
 DON'T MATCH.
 **RISER AND TREAD ON DETAIL 12/A-8 DON'T
 MATCH FLOOR PLANS.
 **REVISE SPACING OF HANDRAIL PICKETS.
 **SPECIFY FIREBLOCKING AS REQ'D BY SEC.
 2305 AT STAIRS.
 C)SPECIFY SIZE OF WASHER FOR GARAGE
 DOOR STRUCTURAL BUCK DETAIL.
 D)DETAIL 4/A-8: CLARIFY SIZE OF STUDS.
 SEE FRAMING PLANS. REVISE FASTENERS
 ACCORDINGLY.
 E)DETAIL 15/A-8: SEE COMMENTS ON SHEET.
  
 11-SHEET A-9: SHEAR WALL SCHEDULE NEED
 ALL INFORMATION. NAILING SIZE, SPACING
 ETC. SEE COMMENTS ON SHEET.
 **UPDATE SEMCO CONNECTORS.
 **WHERE ARE THE SHEARWALL NOTES?. SEE
 COMMENTS ON PLANS.
  
 NOTE: PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 CAD DRAWINGS TO EXPEDITE THE REVIEW
 PROCESS AND CLOUD ALL CHANGES.
  
 12-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR A SEPARATE
 PERMIT.
 13-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS WITH SIZE AS SHOWN ON LIVING
 AND DINING AREA. SEE PLANS.
 14-OWES $285.67 FOR UPDATED VALUATION
 AND RADON FEES.
 15-PROVIDE ATTIC ACCESS AT GARAGE. SEC.
 2309.6 FBC 2001.
 16-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305 FBC 2001.
 17-RESUBMIT PRODUCT APPROVAL FOR ENTRY
 DOORS: NEED UPDATED PRODUCT APPROVAL
 WITH DADE COUNTY LOGO AT BOTTOM OF
 REPORT PAGE AND DRAWINGS WITH THE
 RENEWAL STAMP.
 18-PROVIDE DETAIL SPECS FOR 1 HOUR FIRE
 RATED GLASS BLOCK ASSEMBLY (ARCHITECT)
 **PROVIDE PRODUCT APPROVAL FOR ONE HOUR
 GLASS BLOCK ASSEMBLY (CONTRACTOR).