Plan Review Notes For Permit 03080143 |
Permit Number |
03080143 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-19 00:00:00 | *****CORRECTONS****** | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)ALL EXTERIOR DOORS ARE GLAZED. | | ONE METHOD OF EGRESS ON THE FIRST FLOOR | | MUST BE PROVIDED, CANNOT BE SHUTTERED, | | FBC1005.4.5, 2003 AMENDMENT. | | | | 3.)SUBMIT PRODUCT APPROVALS FOR ALL | | GLAZING, DOORS, ROOF, MULLIONS,SHUTTERS. | | ANY PRODUCT APPROVALS NOT SUBMITTED | | BEFORE THE LAST REVIEW WILL REQUIRE | | SEPARATE PERMITS FOR THOSE ITEMS. | | | | 4.)DETAIL S1-38, THE BOTTOM OF | | FOUNDATIONS SHALL EXTEND NO LESS THAN | | 12" BELOW FINISH GRADE, FBC1804.1.3. | | | | 5.)DETAIL S3-12 ATTACHMENT CONFLICTS | | WITH THE USP 2003 CATALOG.NO UPLIFT | | IS SPECIFIED IN THE CATALOG WHEN 10DX | | 1 1/2 NAILS ARE USED.CHECK ALL | | ATTACHMENTS. | | | | 6.)FEES DUE; $20.44. | | | | 7.)PROVIDE A SOILS INVESTIGATION | | REPORT. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|