Plan Review Notes
Plan Review Notes For Permit 03080127
Permit Number 03080127
Review Stop B
Sequence Number 2
Notes
Date Text
2003-10-07 00:00:00*****PROVISO*****
  
 1.) 30PSF BOTTOM CHORD LIVE LOAD FOR
 ATTICS W/STORAGE, 10PSF NO STORAGE
 FBC TABLE 1604.1.
 2.) FIREBLOCK FOR STAIRS FBC2305.1.4.
 (DETAIL 3-7.1), REVISE.
 3.) FIRESTOP 2ND FLOOR WALL SECTION 7.1
 FBC705.3., REVISE GUARDRAIL/HANDRAIL
 LANGUAGE TO COMPLY FBC1608.2, SUBMIT
 REVISION.
 4.) REVISE SHEET 3.1 TO SHOW DRAFTSTOP
 FBC705.3.
 5.) SEPARATE PERMIT REQUIRED FOR
 HURRICANE SHUTTERS; SUBMIT ATTACHMENT
 SCHEDULE AND PRODUCT APPROVALS.
 6.) DETAIL A-2.1, 4" MIN ABOVE GRADE
 FLOOR ELEVATION, WPB AMEND FBC1804.1.7.
 SUBMIT REVISION.