Plan Review Notes For Permit 03080127 |
Permit Number |
03080127 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-14 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES TO | | PLANS AND RESUBMIT FOR REVIEW. | | | | 1} THE EQUIPMENT GROUND SHOWN FROM THE | | METER TO THE DISCONNECT CREATES A | | PARALLEL RETURN PATH WITH THE NEUTRAL | | AND MUST NOT BE INSTALLED. | | | | 2} PLEASE LIST THE SMALL APPLIANCE | | CIRCUITS PER 220.16(A).THE PANEL | | SCHEDULE ONLY SHOWS 1@ 7500VA. | | | | 3} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | 4} PLEASE SHOW ALL OUTLET SPACING | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | 5} PLEASE NOTE FRONT AND REAR | | RECEPTS REQ`D PER 210.52E | | | | 6} PLEASE NOTE KITCHEN COUNTER- | | -SPACE RECEPT SPACING SHALL MEET ART; | | 210.52C 1,2,3,4,AND 5. | | | | 7} SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT.NFPA-72 8-1.4.1.6.2. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|