Plan Review Notes
Plan Review Notes For Permit 03080127
Permit Number 03080127
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE EQUIPMENT GROUND SHOWN FROM THE
 METER TO THE DISCONNECT CREATES A
 PARALLEL RETURN PATH WITH THE NEUTRAL
 AND MUST NOT BE INSTALLED.
  
 2} PLEASE LIST THE SMALL APPLIANCE
 CIRCUITS PER 220.16(A).THE PANEL
 SCHEDULE ONLY SHOWS 1@ 7500VA.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E
  
 6} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210.52C 1,2,3,4,AND 5.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT.NFPA-72 8-1.4.1.6.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718