Plan Review Notes For Permit 03072437 |
Permit Number |
03072437 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-20 00:00:00 | PROVISO: | | | | 1.BALANCE AIR RETURN - RETURN TRANSFER | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM IT'S SERVING & THE | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. | | | | 2.BATHROOMS SHALL HAVE A WINDOW WITH A | | MINIMUM OF 3 SQ FT CLEAR OPENING OR HAVE | | MECHANICAL VENTILATION. 2001 FBC(M) | | 402.3.1 (REV JUNE 30,2003). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|