Plan Review Notes For Permit 03072431 |
Permit Number |
03072431 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-12 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE PERMIT APPLICAT | | -IION , PLANS AND CONTRACT. | | SHOWS 1 1/2 HP PUMP AND 2HP PUMP, | | PLANS SHOWS HEATER AS N/A AND YET | | WIRING DIAGRAM SHOWS HEAT PUMP BEING | | INSTALLED?? | | IF HEAT PUMP IS BEING INSTALLED, | | PLEASE NREVISE APPLICATION, VALUE FOR | | SCOPE OF WORK. 104.6.5 | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS, | | FOR EXSITING SERVICE AND ALL NEW LOADS | | BEING ADDED. HEAT PUMP, PUMPETC. | | 215-5 | | | | | | 3)NOTE: PLEASE PROVIDE SPEC SHEETS FOR | | HEATER, SHOWINGLISTING . | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|