Plan Review Notes
Plan Review Notes For Permit 03072430
Permit Number 03072430
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-23 00:00:00******* NOTES REDLINED. *****
  
 1)NOTE: PLEASE SEE LT REQ'D ON PATIO.
 210.70, LS 101 5-8
  
 2)NOTE: METERCAN SHOWN AT 150A, PLEASE
 SEE THAT 150A METERCAN IS NOT A COMMON
 SIZE. 100A, 200, 320,400,600A ETC.
  
 3)NOTE: PLEASE SEE 210.52D , RECETP
 TO BE A MAX OF 3'FROM SINK IN MASTERBATH
  
 4)NOTE: PLEASE SEE SERVICE ENT CONDUCTOR
 -S SHOWN AS 2/0'S FOR 200A SERV,??
  
 PLANS TO BE REVISED.