Plan Review Notes For Permit 03072407 |
Permit Number |
03072407 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-20 00:00:00 | *****CORRECTIONS****** | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)ADDITIONAL FEES DUE, $20.56. | | | | 2.)PROVIDE A SOILS INVESTIGATION | | REPORT. | | | | 3.)DETAILS 5-A5, 12-A5, SEMCO | | ATTACHMENTS NO LONGER AVAILABLE. REVISE. | | | | 4.)NAILING FOR THE USP CONNECTORS | | CONFLICT WITH THE USP 2003 CATALOG. | | CHECK ALL ATTACHMENTS. | | | | 5.)DETAIL 38-A1, BOTTOM OF FOUNDATION | | TO BE A MINIMUM OF 12" BELOW GRADE, | | FBC1804.1.3. | | | | 6.)PROVIDE TWO PRODUCT APPROVALS FOR | | ALL GLAZING, SHUTTERS, ROOF, MULLIONS, | | DOORS.ANY PRODUCT APPROVALS NOT | | SUBMITTED WILL REQUIRE A SEPARATE | | PERMIT. | | | | 7.)PROVIDE A HURRICANE SHUTTER | | ATTACHMENT, OR APPLY FOR A SEPARATE | | PERMIT. |
|