Plan Review Notes For Permit 03072377 |
Permit Number |
03072377 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-19 00:00:00 | ******CORRECTIONS****** | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)SEPARATE PERMITS REQUIRED (POOL, | | GAS). | | | | 3.)FIRESTOP REQUIRED, FBC705.3 (REVISE | | WALL SECTION). | | | | 4.)ADDITIONAL FEES DUE (RADON),$47.66. | | | | 5.)SOME ATTACHMENTS ARE NOT CONSISTENT | | WITH THE USP2003 CATALOG EITHER IN | | NAIL SIZE OR NUMBER.NO DESIGN UPLIFT | | WAS GIVEN ON THE PLAN.EXAMPLE: DETAIL | | 19-4S2 SPECIFIES HTA20 WITH 10-10DX | | 1 1/2.USP CATALOG SPECIFIES 13 10DX | | 1 1/2 OR 10 10D FOR 1500 UPLIFT. CONFIRM | | CONNECTIONS AND REVISE IF NECESSARY; | | NOTE ON THE PLAN. | | | | 6.) PROVIDE HURRICANE SHUTTER ATTACHMENT | | SCHEDULE (SEE ATTACHED). | | | | 7.) THERMA-TRU PRODUCT APPROVAL IS NOT | | LEGIBLE AND MAY BE INCOMPLETE.THIS | | MAY BE AVAILABLE FOR DOWNLOAD AT | | WWW.MIAMIDADE.GOV (FIND A DEPT; BUILDING | | CODE COMPLIANCE; PRODUCT CONTROL, SEARCH | | APPROVED PRODUCTS). | | | | 8.) WINDOWS 4,5,6,21,23,24 MUST COMPLY | | WITH FBC2405.1 (SAFETY GLASS). |
|