Plan Review Notes
Plan Review Notes For Permit 03072377
Permit Number 03072377
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-19 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEPARATE PERMITS REQUIRED (POOL,
 GAS).
  
 3.)FIRESTOP REQUIRED, FBC705.3 (REVISE
 WALL SECTION).
  
 4.)ADDITIONAL FEES DUE (RADON),$47.66.
  
 5.)SOME ATTACHMENTS ARE NOT CONSISTENT
 WITH THE USP2003 CATALOG EITHER IN
 NAIL SIZE OR NUMBER.NO DESIGN UPLIFT
 WAS GIVEN ON THE PLAN.EXAMPLE: DETAIL
 19-4S2 SPECIFIES HTA20 WITH 10-10DX
 1 1/2.USP CATALOG SPECIFIES 13 10DX
 1 1/2 OR 10 10D FOR 1500 UPLIFT. CONFIRM
 CONNECTIONS AND REVISE IF NECESSARY;
 NOTE ON THE PLAN.
  
 6.) PROVIDE HURRICANE SHUTTER ATTACHMENT
 SCHEDULE (SEE ATTACHED).
  
 7.) THERMA-TRU PRODUCT APPROVAL IS NOT
 LEGIBLE AND MAY BE INCOMPLETE.THIS
 MAY BE AVAILABLE FOR DOWNLOAD AT
 WWW.MIAMIDADE.GOV (FIND A DEPT; BUILDING
 CODE COMPLIANCE; PRODUCT CONTROL, SEARCH
 APPROVED PRODUCTS).
  
 8.) WINDOWS 4,5,6,21,23,24 MUST COMPLY
 WITH FBC2405.1 (SAFETY GLASS).