Plan Review Notes
Plan Review Notes For Permit 03072336
Permit Number 03072336
Review Stop P
Sequence Number 1
Notes
Date Text
2003-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 SANITARY RISER DIAGRAM, THE
 DRINKING FOUNTAINS AND THE URINAL ARE
 NOT VENTED. SECTION 901.2.1
 2) PER TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 3) FLOORS OF SANITARY FACILITIES SHALL
 BE CONSTRUCTED OF CONCRETE OR OTHER NON-
 ABSORBENT MATERIALS, SHALL HAVE A SMOOTH
 SLIP-RESISTANT FINISH, AND SLOP TO FLOOR
 DRAINS. - FLOOR DRAINS REQUIRED FOR
 HOSEING DOWN TOILET ROOMS. SEC. 403.8.3
  
 REVIEW BY KEN STEVENS